4.1
Selection of the temperature sensors
The case/coldroom controller uses two-wire NTC temperature sensors to perform control.
All sensors connected
must
be the same type and parameters are not set separately for the sensors. The type
of sensor used can be defined by the Sensor Type parameter (Menu 6-2-5).
The NTC following sensor types are usable:
L243 (K243)
Temperature range -50°C to 50°C; Type K243 sensor can be used in place
of type L243. Characteristics of these two sensors are identical.
K277
Temperature range -50 to 50°C
5K3A1
Temperature range 0 to 100°C
For information on the dimensions see chapter 11.3.
Detaillierte Informationen zu den Temperaturfühlern sind dem Datenblatt “Temperaturfühler” zu entnehmen.
Detailed information on the temperature sensors are contained in the data sheet “temperature sensors”.
All due care must be exercised when installing temperature sensors. Sensor leads need not be
shielded when installed exclusively within the refrigerated display case to be controlled and when
interference is not to be expected (for example from power wires running parallel to the leads. Other
wise suitable precautions must be taken to protect the sensor leads from external interference.
An offset can be independently applied to the temperature sensors, which is effective for display and control
functions, see Section 4.4.1.
Summary of Contents for UA 410 L Case Controller
Page 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...