Pin and Terminal Assignments of UA 410 L
50
Firmware V1.50 - Doku 2.0 06. April 2016
6.4
Mode of operation of the relay and transistor outputs
The table shows operation of the outputs for the separate controller types.
Relay outputs 230 V AC
Transistor outputs 24 V DC/50 mA
Controller type
Cooling
Alarm
81, 82, 83
91, 92, 93
UA 410 L
Positive
Invertierted
Without function
Without function
25
26
28
1
positiv
POSITIVE
positive
15
16
18
N
L
invertiert
INVERTED
inversé
Alarm
ALARM
Alarme
Kühlung
COOLING
Réfrigération
Mode of operation „positive”
means that operation of the relay is not inverted:
The relay is energized when the controller activates the function output (e.g. cooling = ON).
(This means that the contact of a normally open relay is closed.)
The relay is not energized when the controller deactivates the function output (e.g. cooling = OFF).
(This means that the contact of a normally open relay is open.)
Mode of operation „inverted”
means that operation of the relay is inverted:
The relay is not energized when the controller activates the function output (e.g. alarm = ON).
(This means that the contact of a normally open relay is open.)
The relay is energized when the controller deactivates the function output (e.g. alarm = OFF).
(This means that the contact of a normally open relay is closed.)
6.5
Terminal assignment of the 230 V AC digital inputs
Warning - hazardous electrical voltage!
Danger of electric shock! BEFORE and AFTER
connection it must checked
that the 230 V AC digital inputs are
off load!
N
L
230 V AC
1
2
3
4
10
1
D32
D31
D22
D21
D12
D11
73
74
43
44
63
64
53
54
2
1
3
4
CAN-GND
CAN-LOW
CAN-HIGH
SHIELD
D42
D41
GND
AO2
GND
AO1
5
0
2
3
1
4
6
7
8
9
5
0
2
3
1
4
6
7
8
9
CAN-BUS
ADDRESS
1..99
ZNG:112 730 DEF3
31
32
30 29
LEDs
Controller Type
D42/D41
D32/D31
D22/D21
D12/D11
UA 410 L
--
Enable/disable
high/low temperature
alarms Rx.6 to Rx.0
Enable/disable
high/low temperature
alarms Rx.1 to Rx.5
Enable/disable
cooling
Summary of Contents for UA 410 L Case Controller
Page 30: ...Function of UA 410 L 24 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 52: ...Installation and Startup of UA 410 L 46 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 72: ...Operation of UA 410 L 66 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 80: ...Menu Structure of UA 410 L 74 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 82: ...Decommissioning and disposal 76 Firmware V1 50 Doku 2 0 06 April 2016 Notice...
Page 92: ...Order numbers and accessories of UA 410 L 86 Firmware V1 50 Doku 2 0 06 April 2016 Notice...