68
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Modbus Map
Modbus
Coil Number
Modbus
Register Number
R/W
DCI Descriptor
Notes
—
300
R
DCI_MOTOR_CONTROL_STATUS
—
4785
—
R
Run—bit 0
—
4786
—
R
—
—
4787
—
R
In Bypass—bit 2
—
4788
—
R
—
—
4789
—
R
—
—
4790
—
R
Fault—bit 5
—
4791
—
R
—
—
4792
—
R
—
—
4793
—
R
—
—
4794
—
R
—
—
4795
—
R
—
—
4796
—
R
Relay 1—bit 11
—
4797
—
R
Relay 2—bit 12
—
4798
—
R
Control From Net—bit 13
—
4799
—
R
Permissive—bit 14
—
4800
—
R
—
—
—
301
R
DCI_ORION_CURRENT_SCALE_FACTOR
Scale factor 10
—
302
R
DCI_RMS_CURRENT_IA
Amps * 10
—
303
R
DCI_RMS_CURRENT_IB
Amps * 10
—
304
R
DCI_RMS_CURRENT_IC
Amps * 10
—
305
R
DCI_RMS_CURRENT_AVG
Amps * 10
—
306
R
DCI_RMS_VOLTAGE_VAB
Volts
—
307
R
DCI_RMS_VOLTAGE_VBC
Volts
—
308
R
DCI_RMS_VOLTAGE_VCA
Volts
—
309
R
DCI_RMS_VOLTAGE_AVG
Volts
—
310
R
DCI_TOTAL_KW
kW * 10
—
311
R
DCI_APPARENT_PF
PF * 100
—
312
R
DCI_POWER_SIGN
—
—
313
R
DCI_FREQUENCY
Freq * 100
—
314
R
DCI_OVERLOAD_THERMAL_PILE
Percent
—
315
R
DCI_CURRENT_UNBAL_PERCENT
Percent
—
316
R
DCI_VOLTAGE_UNBAL_PERCENT
Percent
—
317
R
Reserved
—
—
318
R
DCI_TEMP_POLE_1
Deg C * 10
—
319
R
DCI_TEMP_POLE_2
Deg C * 10
—
320
R
DCI_TEMP_POLE_3
Deg C * 10
—
321
R
DCI_POLE_TEMP_AVG
Deg C * 10
—
322
R
DCI_NUMBER_OF_STARTS
Reset though DCI_COMMAND_REGISTER
—
323
R
DCI_RUN_TIME
Hours, reset though DCI_COMMAND_REGISTER
www.comoso.com
Summary of Contents for S611
Page 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Page 2: ...www comoso com...
Page 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 95: ...www comoso com...