70
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Modbus Map, continued
Modbus
Coil Number
Modbus
Register Number
R/W
DCI Descriptor
Notes
—
402
R/W
DCI_COMMAND_REGISTER
1
= Clear motor run hours
2
= Clear motor start count
3
= Clear fault queue
—
403
R/W
DCI_CONFIGURATION_RESET
1
= Soft reset
2
= Factory defaults
—
404
R/W
DCI_OVERLOAD_FLA
Amps * 10
—
405
R/W
DCI_MOTOR_RATED_VOLTAGE
Volts, 115–600, (Default = 480)
—
406
R/W
DCI_START_METHOD
0
= Vramp
1
= Limit
2
= Pump
—
407
R/W
DCI_START_TIME
Seconds*10, 0.5–180 (20)
—
408
R/W
DCI_INITIAL_TORQUE
%, 0–100 (45)
—
409
R/W
DCI_STOP_TIME
Seconds*10, 0–120 (0, no pump stop option, 50
with pump stop enabled)
—
410
R/W
Reserved
—
—
411
R/W
DCI_KICK_START_TIME
Seconds*10, 0–2 (0)
—
412
R/W
DCI_KICK_START_TORQUE
%, 0–100 (0)
—
413
R/W
DCI_RESET_MODE
0
= Manual
1
= Auto
—
414
R/W
DCI_ENABLE_DISABLE_TRIP
—
6609
—
—
Overload
—
6610
—
—
Jam
—
6611
—
—
Stall
—
6612
—
—
Current Imbalance
—
6613
—
—
Load Disconnect
—
6614
—
—
Phase Loss
—
6615
—
—
Under Voltage
—
6616
—
—
Over Voltage
—
6617
—
—
Voltage Unbalance
—
6618
—
—
Phase Reversal
—
6619
—
—
Ground Fault
—
6620
—
—
Overload On Start
—
6621
—
—
Shorted SCR
—
6622
—
—
SCR Not Firing
—
6623
—
—
Over Temp
—
6624
—
—
—
—
—
415
R/W
DCI_OVERLOAD_TRIP_CLASS
5–30, (20)
—
416
R/W
DCI_JAM_TRIP_LEVEL
%FLA, 150–400 (300)
—
417
R/W
DCI_JAM_TRIP_DELAY_SECONDS
Seconds 1–20 (2)
—
418
R/W
DCI_STALL_TRIP_LEVEL
%FLA, 150–300 (200)
www.comoso.com
Summary of Contents for S611
Page 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Page 2: ...www comoso com...
Page 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 95: ...www comoso com...