26
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Operating Parameters—Pump Option
3.
In the Protection mode, set the Protection parameters to the desired values.
Protection Parameters
Note:
Editing the Trip Class parameter to “OFF” will disable overload protection.
Operating Parameter
Units
Min
Max
Default
Notes
Motor FLA
Amps
Motor FLA parameter
must be set to motor
nameplate FLA to
achieve proper overload
protection
Frame Size A–52
26
52
26
Frame Size A–65
32.5
65
32.5
Frame Size A–77
38.5
77
38.5
Frame Size B–99
48
99
48
Frame Size B–125
62.5
125
62.5
Frame Size C–156
78
156
78
Frame Size C–180
90
180
90
Frame Size D–242
120
242
120
Frame Size E–302
151
302
151
Frame Size E–361
180.5
361
180.5
Frame Size F–414
207
414
207
Motor rated voltage
Volts
200
600
480
—
Start method
0
2
2
0
= Voltage ramp
1
= Current limit
2
= Pump start
Start time
Seconds
0.5
180
20
—
Initial torque
%
0
100
45
—
Stop time
Seconds
0
60
5
—
Kick start time
Seconds
0
2
0
—
Kick start torque
%
0
100
0
—
Auto reset mode
—
0
1
0
0
= Manual
1
= Auto
Advanced config
—
N/A
N/A
N/A
—
Protection Parameter
Units
Min
Max
Default
Trip class
—
Off, 5
30
20
Jam trip
%
Off, 150
400
300
Start stall trip
%
Off, 150
400
200
Current imbalance
%
Off, 1
100
20
Under load
%
Off, 1
50
6
Phase loss
%
Off, 1
100
40
Under voltage
%
Off, 1
99
90
Over voltage
%
Off, 101
120
110
Voltage imbalance
%
Off, 1
20
6
Phase sequence
—
Off, ABC
ACB
ABC
www.comoso.com
Summary of Contents for S611
Page 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Page 2: ...www comoso com...
Page 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 95: ...www comoso com...