58
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Power Losses
The following table lists the maximum power loss for each S611 soft starter when it is
operating in the across-the-line mode with its bypass contactor pulled in. These losses should
be used in conjunction with the losses of another cabinet mounted device to determine the
enclosure size and any cooling requirements.
Maximum Power Loss
Frame Size
FLA Current Range
Power Loss (Watts)
Catalog Number
A
26–52A
32
S611A052N3S
32.5–65A
37
S611A065N3S
38.5–77A
42
S611A072N3S
B
48–99A
44
S611B099N3S
62.5–125A
55
S611B125N3S
C
78–156A
61
S611C156N3S
90–180A
73
S611C180N3S
D
120–242A
100
S611D242N3S
E
151–302A
70
S611E302N3S
180.5–361A
89
S611E361N3S
F
207–414A
110
S611F414N3S