Modbus Map, continued
Modbus
Coil Number
Modbus
Register Number
R/W
DCI Descriptor
Notes
—
442
R/W
DCI_MODBUS_PARITY
0
= Even parity, 1 stop bit (default)
1
= Odd parity, 1 stop bit
2
= No parity, 2 stop bits
3
= Even parity, 2 stop bits
4
= Odd parity, 2 stop bits
5
= No parity, 1 stop bit
—
443
R/W
DCI_COMM_LOSS_TIMEOUT_MILLISECS
Milliseconds, 1–65000 (2000)
—
444
R/W
DCI_COMM_LOSS_BEHAVIOR
1
= Fault (default)
2
= Hold last state
3
= Stop
—
445
R/W
DCI_NETWORK_WATCHDOG_ENABLE
0
= Disable
1
= Enable (0)