S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
57
Note:
Always refer to motor plate FLA and ensure that the motor plate FLA is equal to or
lower than the maximum current value in the tables.
Heavy Duty—500% FLA for 30 Seconds, 125% Continuous
Severe Duty—600% FLA for 30 Seconds, 125% Continuous
Maximum
Current (Amps)
Horsepower Rating
208V
240V
480V
600V
Catalog Number
49
15
15
40
50
S611A052N3S
83
25
30
60
75
S611B099N3S
142
40
60
125
150
S611C156N3S
225
75
75
200
200
S611D242N3S
256
75
100
200
250
S611E361N3S
285
100
125
250
300
S611F414N3S
Maximum
Current (Amps)
Horsepower Rating
208V
240V
480V
600V
Catalog Number
41
10
15
30
40
S611A052N3S
69
20
30
60
60
S611B099N3S
117
30
50
100
125
S611C180N3S
187
60
75
150
200
S611D242N3S
213
75
75
150
200
S611E361N3S
238
75
100
200
250
S611F414N3S