S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
47
Fault History
The S611 stores the last 10 fault codes in a queue stored in non-volatile memory.
This fault queue can be traversed using the following sequence of button presses.
Fault History
Error Codes
The following table describes error messages and codes that can be generated by the S611.
If these error codes cannot be cleared by a reset or power cycle, contact the factory for service.
Error Codes
Locking the User Interface
The ability to modify set-point values from the user interface can be disabled by changing the
User Interface Edit Lock parameter in the Advanced Config parameter.
Step 1:
Press the Fault Log button when the Fault LED is lit. The display
starts flashing, shows the last fault code, and illuminates the corresponding
Protection/Operation LEDs as appropriate to identify the fault.
Step 2:
Press the Down button to view older fault codes or the Up button to
view more recent fault codes.
Step 3:
Press the Fault Log button to exit the Fault Hisory mode. The display
now shows the last fault and is no longer flashing. Pressing Reset will reset
the device if the fault no longer is present and exits the Fault History mode.
Fault Log
F. 10
F. 04
Fault Log
F. 10
Error Code
Description
NC
Communication between the main unit and user interface has been lost
E01
The user interface clock has failed. Pressing RESET on the user interface will allow the user
interface to continue to function, but performance will be degraded
E02
A switch on the user interface is active (stuck) at power-up
E03
The user interface controller has detected an internal error
www.comoso.com
Summary of Contents for S611
Page 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Page 2: ...www comoso com...
Page 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 95: ...www comoso com...