42
S611 Soft Starter
MN03902011E—May 2012 www.eaton.com
Advanced Operation Mode, continued
Code
Parameter
Minimum
Maximum
Default
Notes
P.09
Relay 2 (96, 97, 98)
0
1
0
0
= Faulted
1
= Not faulted
P.10
Relay 1 (13, 14)
0
5
2
0
= Faulted
1
= Not faulted
2
= Run (in bypass)
3
= Not in bypass
4
= Motor energized
5
= Motor not energized
P.11
Start Control (Level/Edge)
0
1
1
1
= Level
0
= Edge
P.12
Jam Trip Delay
1
20
2
—
P.13
Ground Fault Trip Enable
0
1
0
0
= Disable
1
= Enable
P.15
Ground Fault Trip Delay
1
20
2
Value in seconds
P.16
Ground Fault Start Delay
0
20
1
Value in seconds
P.17
Current Imbalance Trip Delay
1
20
5
Value in seconds
P.18
Current Phase Loss Trip Delay
1
20
2
Value in seconds
P.19
Under Load Trip Delay
1
60
5
Value in seconds
P.20
Under Load Source
0
1
0
0
= Trip on low kW%
1
= Trip on under current %
P.21
Under Voltage Trip Delay
1
20
10
Value in seconds
P.22
Over voltage Trip Delay
1
20
10
Value in seconds
P.23
Voltage Imbalance Trip Delay
1
20
10
Value in seconds
P.24
UI Comm Loss Fault Enable
0
1
1
0
= No fault on UI disconnect or comm loss
1
= Faulted
P.25
Shorted SCR Fault Enable
0
1
1
0
= Disable
1
= Enable
P.26
SCR Not Firing Fault Enable
0
1
1
0
= Disable
1
= Enable
P.27
Over Temperature Fault Enable
0
1
1
0
= Disable
1
= Enable
P.28
Overload on Start Enable
0
1
1
0
= Disable
1
= Enable
P.29
Command Register
0
3
0
0
= No action
1
= Clear motor run hours
2
= Clear motor start count
3
= Clear fault queue
www.comoso.com
Summary of Contents for S611
Page 1: ...S611 Soft Starter User Manual Effective May 2012 Supersedes August 2011 www comoso com...
Page 2: ...www comoso com...
Page 12: ...S611 Soft Starter x S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 94: ...82 S611 Soft Starter MN03902011E May 2012 www eaton com www comoso com...
Page 95: ...www comoso com...