13
GREEN MOTION BUILDING INSTALLATION MANUAL
MN191028EN
January 2022 www.eaton.com
00
Title
5 Mounting and installation
5.1 Positioning the Green Motion Building EV charger
The installation position of the Green Motion Building EV charger must meet the following conditions:
•
The EV charger must be installed in a place with relative humidity below 95 %.
•
Optimal operation of the EV charger is in the temperature range -25 °C to +45 °C.
•
Install the EV charger to ensure easy access to the controls and connections.
•
The surface of the wall where the EV charger will be installed must be able to take its weight (max. 8 kg).
•
The EV charger must be used below a maximum altitude of 2000 m above sea level.
•
If the EV charger is targeted to be used by disabled people, refer to national requirements for charging station
accessibility.
•
If the user does not use a wheelchair, a height of 1500 mm from ground level is optimal.
•
The power supply cable and the communication cable are introduced through the cable glands on the bottom of the
EV charger.
Do not mount the EV charger above or under flammable building materials.
Do not install the EV charger in areas where highly flammable substances are present.
Do not install the EV charger in areas subject to explosion hazard.
Make sure there is enough free space for air circulation around the EV charger. Local regulations may
require larger clearances.
To prevent the risk of electric shock or other injury, check that there are no electrical or hydraulic lines in the
walls before drilling the mounting holes of the EV charger.
5.2 Mounting
The EV charger can be mounted directly onto the wall or on a floor-mounted column (optional).
Step 1 .
Use a spirit level to place the drilling template level on the wall. Make sure the template’s top is at a height
of 1500 mm from ground level, for optimal accessibility.
(1)
Step 2 .
Mark the holes with a pencil and remove the drilling template.
Step 3 .
Drill four holes in the wall as shown in Figure 5.
Step 4 .
Place four gaskets around the four slots on the outside of the unit, as shown in Figure 6.
Step 5 .
Fix the unit to the wall with four ø 6-mm screws.
1
Refer to national requirements to make the EV charger accessible to disabled people.
Please note that the appropriate type of wall plugs and screws must be selected by professional and
qualified personnel, based on the following considerations:
•
the installation location,
•
the type of the wall on which the EV charger is to be mounted.
This is to ensure the safest possible mounting of the Green Motion Building EV charger.