The String Log entries include:
•
All String currents
•
Battery temperature
Example log entry:
27-Jun-2018T09:35:50 String currents 1.18, 0.03; temp 27
Date
Time
String 1 current /A
String 2 current /A
Battery temp /
°
C
The Rectifier Log entries include:
•
Bus voltage
•
AC input Voltage
•
Total rectifier current
Example log entry:
27-Jun-2018T09:35:50 AC 231V; rectifier 21.75A, bus 54.99V
Date
Time
ac mains voltage
Total rectifier current
Internal bus voltage
All log entries include:
•
Date and time stamp
The data log sampling rate shall be configurable as below :
•
Logging interval (normal) - bus within trigger limits
10 – 100 mins
•
Rapid log interval (abnormal) - bus outside trigger limits 1 – 10 mins
•
Rapid log threshold (V) - bus voltage trigger limits
Float voltage +/-
1 - 10 volts
Energy LOG entries
The Energy Log includes all 6 load output energy meters and a total load energy meter.
All log entries include:
•
Date and time stamp
Example log entry:
27-Jun-2018T09:35:50
Energy Meters
24.05, 0.00, 25.88, 4.45, 0.00, 45.97; total 327.25
Date
Time
Load energy meters 1 to 6 /kWh
Total energy meter /kWh
The energy log sampling rate is configurable as below :
•
Sampling rate is configurable between 1 – 60 mins