EFX48-xx Series with RM3-340/440 Installation and Operation Guide
146
Copyright © 2019 Eaton Corporation. All Rights Reserved.
IPN March 2019
No AC delay
systemMainsFailDwell
AC fail delay
(s)
60
10
900
10
Over-
current
restart
systemOvercurrentRestartEnable
Restart enable
yes
no
yes
n/a
Interval
systemOvercurrentRestartDelay
Interval (s)
360
60
900
5
Attempts
systemOvercurrentRestartLimit
Retry limit
5
1
9
1
System
nominal
bus
voltage
Float
systemBusVoltageNominal
Float (V)
54.5
39.0
60.0
0.1
* Factory defaults may not be correct for your installation. You need to set-up your own configuration file to
over-write the factory defaults after a factory reset if necessary.