Maintenance and Troubleshooting
Eaton Advanced ePDU User’s Guide P-164000042—Rev 1
www.eaton.com/ePDU
106
343: Output Over Current Warning
Output current amperage (A) reading is greater than the value
configured as the over current warning threshold.
Generates an alarm and is logged in the event log.
Notice
344: Output Over Current Critical
Output current amperage (A) reading is greater than the value
configured as the over current critical alarm threshold.
Generates an alarm and is logged in the event log.
Alarm
345: Output Under Voltage Warning
Output voltage reading is less than the value configured as the low
voltage warning threshold.
Generates an alarm and is logged in the event log.
Notice
346: Output Over Voltage Critical
Output voltage reading is greater than the value configured as the
high voltage critical alarm threshold.
Generates an alarm and is logged in the event log.
Alarm
347: Over Temperature Warning
The temperature level reading is greater than the warning
temperature threshold value.
Generates an alarm and is logged in the event log.
Notice
348: Over Humidity Warning
The humidity level reading is greater than the value configured as
the warning humidity threshold.
Generates an alarm and is logged in the event log.
Notice
349: Internal Temperature Warning
The temperature level reading is greater than the warning
temperature threshold value.
Generates an alarm and is logged in the event log.
Notice
354: L1 Over Voltage Warning
The Phase 1 voltage reading is greater than the value configured as
the over voltage warning threshold.
Generates an alarm and is logged in the event log.
Notice
355: L2 Over Voltage Warning
The Phase 2 voltage reading is greater than the value configured as
the over voltage warning threshold.
Generates an alarm and is logged in the event log.
Notice
356: L3 Over Voltage Warning
The Phase 3 voltage reading is greater than the value configured as
the over voltage warning threshold.
Generates an alarm and is logged in the event log.
Notice
361: Group Under Current Critical
Group input current amperage (A) reading is greater than the value
configured as the low current critical alarm threshold.
Generates an alarm and is logged in the event log.
Alarm
362: Group Over Current Warning
Group current amperage (A) reading is greater than the value
configured as the over current warning threshold.
Generates an alarm and is logged in the event log.
Notice
363: Group Over Current Critical
Group current amperage (A) reading is greater than the value
configured as the over current critical alarm threshold.
Generates an alarm and is logged in the event log.
Notice
Table 18. Alarms, Notices, and Events (Continued)
Alarm Number: Name
Description
Type