1 : fan ON
99
Fan speed UP/DOWN
Fan
DPT 1.007
1 bit
CW
This object is used to switched one fan speed further up or down via 1-bit telegram.
0 : fan speed DOWN
1 : fan speed UP
100
Status fan ON/OFF
Fan
DPT 1.001
1 bit
CT
The status of fan coil channel is visible via this communication object.
0 : complete fan coil channel inactive (all outputs OFF)
1 : any output of fan coil channel is switched ON
101
Status fan speed
Fan
DPT 5.010
1 byte
CRT
This object is used to display the fan speed via 1-byte object.
Hex
Fan Speed
00
0 (Fan OFF)
01
Fan speed 1
02
Fan speed 2
03
Fan speed 3
102
Status fan speed 1
Fan
DPT 1.001
1 bit
CRT
103
Status fan speed 2
Fan
DPT 1.001
1 bit
CRT
104
Status fan speed 3
Fan
DPT 1.001
1 bit
CRT
Only visible if the
Enable communication object “Status fan speed x” 1 bit
is configured to yes.
0 : fan level x deactivated
1 : fan level x activated
105
Forced operation
Fan
DPT 1.003
1 bit
CW
This object used to set fan desired forced position independently from the control value.
0 : no forced operation
1 : forced operation
106
Automatic ON/OFF
Fan
DPT 1.003
1 bit
CW
This object is used to switch the automatic mode. Automatic mode is switched off, if a telegram is
received on a direct communication object.
If the
object value “automatic ON/OFF” switched on to automatic
parameter is selected “1”;
0 : automatic operation OFF
1: automatic operation ON
If the
object value “automatic ON/OFF” switched on to automatic
parameter is selected “
0
”;
0 : automatic operation ON
1: automatic operation OFF