Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 72 / 80
An adjustment can be made as to whether a value telegram is to be sent as a reaction to a short and / or
long button press action when a push button is pressed or released. Additionally, it is possible to
configure whether the value associated with the long button press action is sent via a second object.
1 bit [0 / 1] DPT 1.001 switch command
2 bit [0…3] DPT 2.001 for
ced operation
1 byte [0…255] DPT 5.001 brightness value
2 byte [-
32768…32767] DPT 7.001 signed value
2 byte [0…65535] DPT 8.001 unsigned valu
e
4 byte [float value] DPT14.068 temperature
4 byte [0…
4294967295
] DPT12.001 value unsigned
8
Shutter upper limit position
Input a
DPT 1.002
1 bit
CW
This object the shutter actuator indicates is it is in the upper limit position. This object is used for 1
button options.
0: No Upper end limit
1: Upper end limit
8
Value (temperature)
Input a
DPT 14.068
32 bit
CT
The value type is selected “floating point” this object is created. For more i
nformation look
Value
communication object.
9
Shutter lower limit position
Input a
DPT 1.002
1 bit
CW
This object the shutter actuator indicates is it is in the lower limit position. This object is used for 1
button options.
0: No Lower end limit
1: Lower end limit
9
Value (temperature) - long
Input a
DPT 14.068
32 bit
CT
The value type is selected “floating point” this object is created. For more information look
Value
communication object.
6.3
Switch Object Description
No
Object name
Name
DTP Type
Length
Flags
95
Switch
Output A1
DTP 1.001
1 bit
CW
This object is used to switching of relay. If a logic operation is enabled, the output is calculated via logic
combination.
The object is;
0 = switched ON
1 = switched OFF
96
Status switch
Output A1
DPT 1.001
1 bit
CRT
The current switching state of the channel is saved in the status object. It can be transmitted
automatically its state changed.