step switch
This parameter can be used to select the properties of fan. Please look the fan technical data.
▪
Set the parameter to “changeover switch”;
In this mode delay between two fan speeds. This delay time can be configured via
delay
between fan speed switching in ms [50…5000]
parameter.
▪
Set the parameter to “
step switch
”;
In this mode current fan speed must be switched on for a least time before the new fan
speed is switched on.
Delay between fan speed switching
in ms[50…5000]
50…
*500
…5000
If the
Fan operation mode
parameter is selected
“
changeover switch
”
, this parameter is visible. This
parameter is used to configure the fan delay time. This time is using between the fan speed
switching.
Fan speed on bus voltage failure
unchanged
*off
1
2
3
Using this parameter, the fan reaction can be set after bus voltage failure is set.
Fan speed on bus voltage recovery
unchanged
*off
1
2
3
Using this parameter, the fan behavior is defined after bus voltage recovery is set.
Enable forced operation
yes
*no
This parameter is used to enable fan-forced operation.
Forced operation on object value
0
*1
This parameter is selected which value is activated the forced operation.
Limitation on forced operation
3, 2, 1, OFF
*unchanged
…
This parameter is selected the forced operation behavior.
Enable automatic operation
*yes
no
This parameter can be enabled the automatic control. Automatic control meaning is limited reaction
according to “Control input”.
Enable direct operation
yes