Reaction to OFF telegram
*
switch off
ignore
After this parameter selected ‘switching off’, ignored ‘Enable staircase function’ communication
object ‘disable’ command.
Staircase time can be changed by object
yes
*
no
‘Staircase lighting duration’ communication object is visible if a ‘Staircase time can be changed by
object’ parameter selects ‘yes’. This communication object is 2 byte. The value defines the staircase
on time in second.
NOTE: After a bus voltage fails, staircase on time returns default value (Duration of staircase lighting).
Restart staircase after “Permanent ON”
yes
*
no
If this parameter is selected ‘yes’, receive ‘Permanent ON’ communication object after restart
staircase function.
Activate pre-warning time?
yes
*
no
The warning function can be activated by this parameter select ‘yes’. Then, you can adjust pre
-
warning time, number of pre-warning and time for pre-warning interval. The warning function is for
warning that the staircase lighting time run out and the lights are switched off soon. In the warning,
lights short turn off. Switch status is ON until finish warning time.
Pre-
warning time Minutes (0…59)
Second (0…59)
*0…59
0…*
30
…59
How long the lights shall be switched on in the period.
Number of pre-warni
ng (1…10)
1…*
2
…10
Enter the number of how many blink doing in the warning.
Time for pre-warning intervals
Seconds (0…59)
0…*
3
…59
How long the lights shall be switched off in the period.
Activate on delay
yes
*
no
This parameter is used delay to switch off position before staircase start.