Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 37 / 80
4.4.2.1
A1 - Staircase Function
If you want to use staircase function, you must have been enabled ‘Staircase’ on the function
windows. Than required parameters and communication, objects are visible. The staircase function
can be parameterized for each channel.
Staircase function has
a three communication object. These are “Enable staircase function”,
“Staircase lighting duration” and “Permanent ON”.
Duration of staircase lighting [min]/ [sec]
0…
*5
…
240[min]
*
0
…59 [sec]
Staircase function on time is calculated by “duration of staircase lighting”. Staircase lighting time is
defined by this parameter. At the end of the on time, the relay off or active the staircase warning
functions.
Staircase retrigger
*
not retriggerable
yes retriggerable
up to staircase lighting time 2x
up to staircase lighting time 3x
up to staircase lighting time 4x
up to staircase lighting time 5x
This parameter defines whether the staircase on time can be retrigger able or not so the on time can
be extended by ‘Enable staircase function’. You can repeat retrigger function until the repeater count
reached the maximum value (2x, 3x, 4x, 5x). If the parameter selects ‘not retriggerable’, staircase on
time doesn’t
extend.