The object is;
0 = do nothing
1 = trigger
6.4
Blind Object Description
95
Move blind/shutter up-down
Output A
DPT 1.008
1 bit
CW
When the telegram is received from bus, blind is moved to the direction (the value 0 or 1) of movement
of the set time.
The object is;
0 = up
1 = down
96
Slat adjustment/stop up-down
Output A
DPT 1.007
1 bit
CW
While blind is moving, the telegram is received then the blind movement is stopped. Other time the
blind slat can be adjusted.
The object is;
0 = stop/slat move one step open
1 = stop/slat move one step close
97
Blind/shutters up-down limid
Enable limitation
Output A
Output A/B
DPT 1.008
DPT 1.003
1 bit
CW
This communication objects are controlled by “Limit travelling range” parameter.
Blind up or down end
position can be limited by this communication object. The blind stops automatically when the configured
upper or lower end position have been reached. After the bus voltage, return object value is set to 0 so
this meaning upper end position is limited.
For the first communication object “
Blind/shutters up-down limit
”;
0 = limited upper end position active
1 = limited lower end position active
For the second communication objet
“Output A/B, Enable limitation”
0 = limitation disable
1 = limitation enable
98
Move to position height 0…255
Output A
DPT 5.001
1 byte
CW
If device is received this telegram, the blind is moved to height determined by the percentage of value.
After the blind moving operation is finished, the slats are returned its previous position.
While the blind is moving
, the “Move slat 0…255” command is received from the bus. If the blind is
reached its target position, the slats are set to the received position.
The object is;
0
= upper end position %0