Product Manual RCUXXYY
EAE KNX Room Control Unit
RCUXXYY PM R1.0
©
EAE Technology
www.eaetechnology.com
Page 4 / 80
1.2
Technical Data RCUXXYY Series
Type of protection
IP 20
EN 60 529
Safety class
II
EN 61 140
Power supply :
- Voltage
21V… 30V DC, SELV
- Current consumption
≤ 10 mA
External supply
-
-
Connections
- Screw terminals
- Max tightening torque
0,5…3,31 mm² solid and stranded wire
0,5…3,31 mm² stranded wire with
ferrule
0.5 Nm
- KNX
Bus connect terminal
Output
- Number
XX output
- Switching voltage
250 V AC; 50/60 Hz
- Switching current 250 V AC
- Switching current 250 V AC,
capacitive loads
16A / AC 1
16A (200
µ
F)
- Maximum switching power
4000 VA
- Mechanical life
> 1 x 10
6
Type of load
- Incandescent lamp
4000 W
- Halogen lamp
4000 W
- Inductive loads, transformer
2000 W
- Electronic drivers
1500 W
Type of contact
- Potential-free, bistable
Input
- Number
YY binary inputs
- Scanning voltage
5 V pulsed
- Current
1 mA
- Cable length
< 300 m
Installation
- 35mm mounting rail
EN 60 715
Operating elements
- LED (red) and button
For physical address
Temperature range
- Ambient
-
5° C + 45° C
- Storage
-
25° C + 55° C
Humidity
- max. air humidity
85 % no moisture condensation
Dimensions
Width W in mm
Width W in units (18 mm modules)
66 x W x 90mm
180 mm
10 modules
Weight
0,65 kg
Box
Plastic, polycarbonate, colour grey
CE
In accordance with the EMC
guideline and low voltage
Application program
Communications
objects
Number of addresses(max)
Number of
assignments(max)
254
255
255
Type of protection
IP 20
EN 60 529
Safety class
II
EN 61 140
Power supply :
- Voltage
21V… 30V DC, SELV
- Current consumption
≤
10 mA
External supply
-
-
Connections
- Screw terminals
- Max tightening torque
0,5…
4 mm
² solid and s
tranded wire
0,5…2,5mm² stranded wire with ferrule
0.8 Nm
- KNX
Bus connect terminal