48
9.3.6.2 Trip counter for 32 channels
Byte [2] contains the number of trippings since the trip counter was last reset.
value range:
0 ... 255
data length:
1 byte (unsigned character)
9.3.6.3 Trip reason for 32 channels
Byte[3] holds the latest reason for trip of the channel.
value range:
0, 1, 2, 4
data length:
1 byte (unsigned character)
byte [2]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte [3]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
no reason for trip available (0)
0
0
0
0
0
0
0
0
short circuit (1)
0
0
0
0
0
0
0
1
overload (2)
0
0
0
0
0
0
1
0
internal failure (4)
0
0
0
0
0
1
0
0
fig. 50: Diagnosis channel: trip counter
fig. 51: Diagnosis channel: reason for trip
1)
available from revision D
fig. 49: Diagnosis channel: error memory
byte [1]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
no parameters available
0/1*
error parameter memory
0/1*
error programme memory
0/1*
error data memory
0/1*
error control unit
0/1*
reset through watchdog
0/1*
reserve
reserve
* error not available = 0 / error available = 1
9.3.6.1 Error memory for 32 channels
Byte[1] holds the internal error memory of the circuit protector.
value range:
0 – 255
data length:
1 byte (unsigned character)
Summary of Contents for ControlPlex EM12D-TIO