9.3.1.2 Configuration data of the EM12D-TIO intelligent supply module (index 200)
When reading index 200, one byte is returned, this index can also be described.
This byte holds the configuration data of the EM12D-TIO intelligent supply module. Evaluation is bit-wise.
value range:
0 – 255
default value:
power saving mode de-activated, freeze active.
data length:
1 byte (unsigned character)
Bit 1
unfreeze = 0 all load outputs (channels) of the circuit protectors are switched off and the EM12D-TIO changes into the
operating mode »Independent operation«.
freeze = 1 all load outputs (channels) of the circuit protectors remain in their current condition and the EM12D-TIO changes
into the operating mode »Independent operation«.
Bit 2
power saving mode
deactivated = 0
power saving mode
activated = 1
byte [1]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
reserve
offline behaviour
(unfreeze/freeze)
0/1
power saving mode
0/1
reserve
reserve
reserve
reserve
reserve
fig. 42: Configuration data EM12D-TIO