9.3.5 Load voltage and load current channel for 32 channels
When reading the index 401– 432, four bytes each are returned.
Byte [1] - byte [2] contain the load voltage of the channel.
value range:
0 – 65535
data length:
1 word (unsigned integer)
The load current is made available as a standardised 16-bit-value with a solution of 10 mA.
Example: measuring value operating voltage = 2512
-> real measuring value = 25.12 Volt.
9.3.6 Extended diagnostic messages (dynamic info) channel for 32 channels
When reading the index 501– 532, three bytes each are returned.
fig. 47: Load voltage channel
byte[1] (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte[2] (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
Byte [3] - byte [4] contain the load voltage of the channel.
value range:
0 – 65535
data length:
1 word (unsigned integer)
fig 48: Load current channel
byte[3] (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte[4] (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
The load voltage is made available as a standardised 16-bit-value with a solution of 10 mV.
Example: measuring value operating voltage = 2512
-> real measuring value = 25.12 Volt.