53
9.3.9.3 Mean value current for 32 channels
1)
Byte[7] – byte[8] contain the mean current value of the channel since the last reset.
value range:
0 ... 65535
data length:
1 word (unsigned integer)
The mean current value is made available as standardised 16 bit value with a resolution of 10 mA (resolution of the channel is one
decimal place, for simplification it is shown identically with the voltage with 2 decimal places).
Example: measuring value operating voltage = 710
-> real measuring value = 7.10 Ampere.
9.3.9.4 Minimum voltage for 32 channels
1)
Byte[5] – byte[6] contain the lowest mean current value of the channel since the last reset.
value range:
0 ... 65535
data length:
1 word (unsigned integer)
The minimum voltage is made available as a standardised 16-bit-value with a resolution of 10 mV.
Example: measuring value operating voltage = 2512
-> real measuring value = 25.12 Volt.
byte[7] (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte[8] (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte[5] (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte[6] (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
fig. 59: Mean value current channel
fig. 60: Minimum voltage channel
1) available from revision D
Summary of Contents for ControlPlex EM12D-TIO
Page 1: ...User Manual ControlPlex EM12D TIO Intelligent Supply Module...
Page 5: ...5...
Page 55: ...55...
Page 58: ...58 Notes...
Page 59: ...59 Notes...