30
9.2 Data model for max. 16 channels
9.2.1 Configuration data of the EM12D-TIO intelligent supply module
9.2.1.1 Internal cycle time (index 198)
2)
When reading index 198, one byte is returned.
The internal cycle time depends on the number of connected circuit breakers.
value range:
100 ms – 610 ms
data length:
1 word (unsigned integer)
9.2.1.2 Configure controllability of the channels with 16 channels (PLCLock Index 199)
1)
When reading index 199, one byte is returned, this index can also be edited.
The status PLCLock value is fed back for all possible 16 channels via one word,
with one bit each representing the status of a channel:
value range:
0 – 65535
data length:
1 word (unsigned integer)
Setting the bit means that the channel cannot be switched on or off via the control unit. This means that voltage is applied to the
output of the channel when the supply voltage is switched on (provided the channel has not tripped previously)
byte [0]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
PLCLock channel 1
0/1
PLCLock channel 2
0/1
PLCLock channel 3
0/1
PLCLock channel 4
0/1
PLCLock channel 5
0/1
PLCLock channel 6
0/1
PLCLock channel 7
0/1
PLCLock channel 8
0/1
byte [1]
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
PLCLock channel 9
0/1
PLCLock channel 10
0/1
PLCLock channel 11
0/1
PLCLock channel 12
0/1
PLCLock channel 13
0/1
PLCLock channel 14
0/1
PLCLock channel 15
0/1
PLCLock channel 16
0/1
fig. 20: PLC Lock (controllability) of channels