10
Use of the terminals for applications not provided for in the operation manual or improper connection can lead to mal-
function or destruction of the device.
The EM12D-TIO intelligent supply module is supplied with voltage both via the supply terminals LINE+ and 0 V and via
X81 COM. The voltages are decoupled reciprocally.
3.3.3 LED »CE/CM«
The LED CE/CM shows the status of the communication unit. Available LED colours are red, green and orange. For further details
please see fig. 9. Illustration of operating modes.
3.4 Representations of the manufacturing date, the Device ID and revision status of the
software
1. supply voltage
IO link L +24V
2. data line
IO link C/Q (to IO link master)
3. supply voltage
IO link L-
3.3.2 Connector socket for the IO link Master
®
, connector socket X81
This connector socket serves for connecting the EM12D-TIO
intelligent supply module with the superordinate IO link master.
Connection of the device with the master is realised with a
one-to-one wiring mode. Preferably the connection should be
a typical sensor cable 3-pole with a cross section of 0.25 mm²
to 0.5 mm² (e.g. FD Li9Y11Y or LifYY). The cable does not have
to be shielded specially. The cable length between the IO link
master and the IO link device must not exceed 20 m.
fig. 4: IO link connection
fig. 5: marking of date code
date code
Device ID
revision status of firmware
Entrance Module
EM12D-TIO-000-DC24V-40A
E-T-A
D-90518 ALTDORF
Made in Germany • xxxx • xxxxx • x
G E R M A N Y
LOAD+ 2.1 (2.2)
COM
ADDR
LINE+1
EM12D-T
max. 16 channels
REX12D-T
0 V
IO-Link