9.3.3 Parameters of channel for 32 channels
When reading the index 101 – 132, two bytes each are returned (with 32 channels).
9.3.3.1 Current rating for 32 channels
The parameter in byte [1] returns the current rating of the channel in Ampere.
The edit command of this value will be ignored for devices with fixed current ratings and will be adopted for the adjustable ones.
value range:
1 – 10 (integer)
default value:
–
data length:
1 byte (unsigned character)
9.3.3.2 Limit value load current for 32 channels
The parameter in byte[2] determines at how many percent of the rated current the channel will signal »limit value exceeded«
This parameter allows read/write transactions.
value range:
50 % – 100 % (whole numbers)
default value:
80 %
data length:
1 byte (unsigned character)
fig. 45: Device parameters channel: limit value load current
fig. 44: Device parameters channel: Rated current
byte [1]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
example: 2
0
0
0
0
0
0
1
0
byte [2]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
example: 100%
0
1
1
0
0
1
0
0