9.2.5 Load voltage channel for 16 channels
When reading the index 401 – 416, two bytes each are returned (with 16 channels).
Byte[1] - byte[2] contain the load voltage of the channel
value range:
0 – 65535
data length:
1 word (unsigned integer)
The load voltage is made available as a standardised 16-bit-value with a solution of 10 mV.
Example: measuring value operating voltage = 2512
-> real measuring value = 25.12 Volt.
9.2.6 Extended diagnostic messages (dynamic info) channel for 16 channels
When reading the index 501 – 516, three bytes each are returned (with 16 channels).
9.2.6.1 Error memory for 16 channels
Byte[1] holds the internal error memory of the circuit protector.
value range:
0 – 255
data length:
1 byte (unsigned character)
fig. 26: Load voltage channel
fig. 27: Diagnosis channel: error memory
byte[1] (LOW)
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte[2] (HIGH)
bit 15
bit 14
bit 13
bit 12
bit 11
bit 10
bit 9
bit 8
description
32768
16384
8192
4096
2048
1024
512
256
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
byte [1]
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
description
128
64
32
16
8
4
2
1
value
0/1
0/1
0/1
0/1
0/1
0/1
0/1
0/1
no parameters available
0/1*
error parameter memory
0/1*
error programme memory
0/1*
error data memory
0/1*
error control unit
0/1*
reset through watchdog
0/1*
reserve
reserve
* error not available = 0 / error available = 1