G 3800 X036 Operation Manual
August 2006
Menu Item:
Explanation:
Description
This text is used as description for the selected Counter address
when accessing the logged data via Dupline-Online.
Factor
Defines the ratio of pulses per unit of measure. If eg an Energy-
meter with 640 pulses/kWh is used, then the figure 640 must be
entered to get the correct kWh reading from the Dupline-Online
database.
6.5.3. Time-based logging of Counters
The set-up for the logging of Counter values is performed in the menu “Mux Counters Log Set-up”. A table
showing the counter addresses available (as defined in the menu “Counter and Mux Analog Setup”) is used
for selecting the Counter addresses to be logged, and for metering text descriptions, scaling for these coun-
ters and engineering units. Also, the Log Time Interval for Counters is defined in this menu.
A Counter address is selected for logging by double-clicking on it with the mouse. The color of the associat-
ed field will then change to Cyan, and this indicates that the parameters entered under "Description", "Factor"
and "Unit of measure" will now be assigned to this Counter address. The color of the field turns green when
another menu or Counter address is selected, to indicate that the Counter address has now been configured
for logging. To change a parameter for a Counter address, click on the associated green field and it will change
color to cyan to indicate that the parameters shown belongs to this Counter address and that it is ready for
changes.
To disable logging for a Counter, double-click on the associated green field.