Object
Function
Channel
In-/ outputs
Relay Output
Pump
A1
Temperature AnaLink
temperature
B1
Temperature AnaLink
temperature
B2
Temperature AnaLink
temperature
Configuration B3
AnaLink Temperature
3 temperature measurements
B1,B2 and B3
MultiGate
Controls the Pump
A1
Application Example
Task:
A pump needed to be started, upon request from 3 different temperature sensors.
Solution:
Use for example 3 AnaLink temperature transmitter, coded for B1,B2 and B3.
Assign address A1 to one of the outputs of a relay module.
Configure channel A1 in the Mastergenerator as a Multigate with Or function.
Set-up ‘One’s’ in the MultiGate matrix B1,B2 and B3.
Configure the 3 AnaLink sensors, to activate their output when temperature is below
eg. 18 degrees.
2.2.10. Thermostat
Description: The Thermostat operates similar to the Push-button function, but is used to indicate an address
occupied by a digital thermostat transmitter.
Parameters: None
* Function: Monostable
* Application: Indicate address used for Digital Thermostat transmitter
G 3800 X036 Operation Manual