G 3800 X036 Operation Manual
August 2006
82
© 2006 Carlo Gavazzi Industri A/S. All rights reserved
The all-OFF function can be implemented the following way:
1. In each of the 3 Mastergenerators, a master function is defined on address E2 for turning OFF all lights on
the local Dupline network.
2. The all-OFF pushbutton on the lower floor is coded E2 and will therefore turn OFF all lights on the lower
floor when activated, as desired.
3. In the Mastergenerator on the middle floor, an External Reference has to be defined for the local Master
Function on address E2 in order to enable the all-OFF pushbutton on the lower floor to trigger it. The
reference is therefore made to address E2 on the Dupline network with ID no 1.
4. In the Mastergenerator on the top floor, an External Reference has to be defined for the local Master
function on address E2 in order to enable the all-OFF pushbutton on the lower floor to trigger it. The
reference is therefore made to address E2 on the Dupline network with ID no 1.
5. Activating the E2 pushbutton on the lower floor will now activate not only the local all-OFF
Master Function on the lower floor, but also the all-OFF Master Functions on the middle and
top floors, and thereby the desired function is achieved.
In the above example, the master function is assigned to address E2 in each Dupline network, but obviously,
it is not necessary to use the same address. The addresses can be completely different, if desired.
2.7.3. Read external input
This function is only available for addresses used for Analink signals. The function makes it possible to use
the Analink value transmitted on one Dupline network in all the other Dupline networks. If for example the sig-
nal from a wind speed sensor is transmitted on the top floor Dupline network, then the "Read External Input"
function makes it possible for the Mastergenerators on the lower floors to use the wind speed value for con-
trol of the local roller blinds.
Parameter
Description
Read External Input
If selected, the Mastergenerator reads the Analink value from an external
address.
Net No / Channel
Defines the Dupline Network ID no and address from where the Analink value
shall be read.