G 3800 X036 Operation Manual
August 2006
98
© 2006 Carlo Gavazzi Industri A/S. All rights reserved
Menu Item:
Explanation:
Description
This text is used as description for the selected channel address
when accessing the logged data via Dupline-Online.
Other languages can be inserted in the 3-language menu.
Log Data to GSM
6.5. Time-based logging
6.5.1. Introduction
This method can be used for Analink signals, Multiplexed analog signals and Counter values. For each of these
3 signal categories, a logging time interval in the range from 5 minutes to 1 month can be defined. The signals
within each category are then logged on a continuous basis according to the selected time interval. The Log
Record contains the Address, all the logged values within this category and time/date/year of the Log Record.
6.5.2. Time-based logging of Analink channels
As described in sec 6.4, the selection of which Analink channels shall be included in time-based logging is
done under the individual channel set-up by choosing the "Log Data to GSM" option. The Analink Log Time
Interval must be defined in the menu "Analink Log set-up".
Menu Item:
Explanation:
Log interval
Defines the time interval between Analink Log Records.
Date
Only relevant when Analink signals are logged on a monthly basis.
Defines the day of the month on which the Log Record shall be
made.
Hour and Minute:
Only relevant when Analink signals are logged on daily basis.
Defines the time of the day on which the Log Record shall be
made.
If selected for a digital channel, the Mastergenerator will send a
log record to the Dupline-Online Webserver each time this
Dupline channel changes status from OFF to ON or ON to OFF.
If selected for an Analink channel, the Mastergenerator will
send a Log Record each time the Analink value crosses one of
the user-defined limits, and whenever the log interval time
selected in the menu “Analink Log Set-up” (see section 6.5) has
passed since last time-based log.
Note: The menu Item text is dynamic, so if “automatic logging”
has been selected for COM2 int he Communication setup-