CAN Interface Specification
057-281 ISSUE: 1
Page 52 of 58
8.2.2.2
READ COMMAND
This command is used to write the requested data to the specified data address.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
0x02
Data Address (16 bit)
Unused
Read Response
A Read Command is responded to with the Read Response to confirm the receipt of the command
and return the data requested.
The only valid Error Code for a Read Command is to indicate an Invalid Read Address.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
0x82
Data Address (16 bit)
Value (32 bit)
Error Code
8.2.2.3
STORE CONFIGURATION COMMAND
This command is used to instruct the DSEA108 to store the configuration in
Non-
Volatile
Memory
.
This ensures all changed values are retained should the DSEA108 be powered down.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
0x03
Unused
Store Configuration Response
A Store Configuration Command is responded to with the Store Configuration Response to confirm
the receipt of the command.
The only valid Error Code for a Read Command is to indicate Configuration Write Failure.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
0x83
Error Code
8.2.2.4
ALARM RESET COMMAND
This command is used to instruct the DSEA108 to reset any active alarm.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
0x04
Unused
Alarm Reset Response
An Alarm Reset Command is responded to with the Alarm Reset Response to confirm the receipt of
the command.
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
0x84
Error Code