CAN Interface Specification
057-281 ISSUE: 1
Page 54 of 58
Data Addresses Continued.
R/W:
Read/Write
R:
Read Only
Index
Description
Range
Type
Scaling and units
59
Output limit overshoot
0 to 300
R/W
1 %
60
Output limit overshoot delay
0 to 100
R/W
0.1 s
61
Soft Start Ramp Start Point (%)
100 to 900
R/W
0.1 %
62
Soft Start Ramp Rate (% / Hz)
50 to 1000
R/W
0.1 %/Hz
63
Start-up Fail Delay
10 to 100
R/W
0.1 s
64
Loss of Feedback Delay
1 to 100
R/W
0.1 s
65
Over Excite Trip
100 to 1500
R/W
0.1 V
66
Over Excite Delay
1 to 50
R/W
0.1 s
67
External Potentiometer OC Alarm Enable
0 / 1
R/W
0:
Disabled
1:
Enabled
66-199
Reserved
200
Generator Frequency
R
0.1 Hz
201
Generator Voltage
R
0.1 V
202
Droop Current
R
0.001 A
203
Excitation Voltage
R
0.1 V
204
Auxiliary Voltage
R
0.1 V
205
External Potentiometer
R
Ohms
206
External Voltage
R
0.01 V
207
Status Flags
R
See
Status Flag List
208
DIP Switch Positions
R
See
DIP Switch Position List
209
Software Version
R
Byte3:
0
Byte2:
Major Version
Byte1:
Minor Version
Byte0:
Build Nuber
210
Bootloader Version
R
Byte3:
0
Byte2:
Major Version
Byte1:
Minor Version
Byte0:
Build
300
Number of stability selections
R
301
Number of alternative selections
R
302
Maximum Excitation Output Offset
R
0.1 %
303
Soft Start Ramp Start Point Minimum
R
0.1 %
304
Soft Start Ramp Start Point Maximum
R
0.1 %
305
Soft Start Ramp Rate Point Minimum
R
0.1 %/Hz
306
Soft Start Ramp Rate Point Maximum
R
0.1 %/Hz
307
Droop Maximum
R
0.1 %
8.2.4.1
STATUS FLAG LIST
Status Flags
(Address 207) are described as follows:
Bits
Description
0 & 1
Configuration File Lost
2 & 3
Start-up Fail Trip
4 & 5
Over Excite Trip
6 & 7
Loss of Feedback Trip
8 & 9
Under Frequency Trip
10 & 11
Potentiometer Fault
12 & 13
UFRO Active
14 & 15
Integral Limit Active
16 & 17
Current Limit Reached
18 to 31
Not Used (all bits set to 1)
Where the status is shown by the following bit patterns:
Value (binary)
Meaning
00
Off
01
On
10
Error (Not Used)
11
Unimplemented