Setup Procedure
057-281 ISSUE: 1
Page 18 of 58
Using DSE Configuration Suite PC
Software, select the appropriate
Voltage
Set Point
.
The
Low Voltage Range
(for 90 V to 300
V systems) or
High Voltage Range
(for
180 V to 600 V systems).
This voltage refers to the voltage applied
to the AVR
L
and
N (L2)
terminals (the sensing
voltage).
Now select the
Set Point
menu
and ‘uncheck’
the
Preset Enable
option.
This allows the
Set Point
parameter to be
configured.
Leave the
Droop
and
External Bias
settings in their default states initially, these are to be addressed
later.
Using DSE Configuration Suite PC
Software, select the appropriate
Frequency Range
(50 Hz or 60 Hz).
Uncheck the
Preset Enable
option.
This allows
Under Frequency Roll
Off Knee Point
to be adjusted if
required.
To ease setup, adjust
Knee Point
to
a low value to prevent
Under
Frequency Roll Off
from activating
during the setup procedure.
Set the
Under Frequency Trip Point
as required.
‘Uncheck’
Preset
Enable
....
and configure the
Set Point
.
‘Uncheck’
Preset
Enable
....
and
configure
the
Knee
Point