Setup Procedure
057-281 ISSUE: 1
Page 28 of 58
4.3.3.2
PRE-DEFINED DROOP SETUP
NOTE: When completing a pre-defined droop setup, the DSEA108 must be wired as shown
to match the selected topology in Configuration Suite. Failure to do so causes erroneous
droop operation.
The pre-defined droop setup procedure is
identical to the
User Configured
setup
procedure in all aspects other than the
Droop
CT AC System
and
Offset Angle
settings. When
the alternator wiring topology is known, it may
be selected from the
Droop CT AC System
drop-down menu. Pre-defined
Droop CT AC
System
parameters automatically fix the
Offset
Angle
to the correct value.
DSE Configuration Suite PC Software shows
the location that the droop CT MUST be fitted.