Section 2: Installation
Table 2-12 Standby Battery Guide
Battery Size
Desired Standby Time
4h
12h
24h
36h
4Ah
700mA
------
------
------
7Ah
700mA
500mA
250mA
------
14Ah
(use 2 x 7Ah batteries
connected in parallel,
UL/ULC installations
only )
700mA
470mA
------
18Ah
------
------
------
300mA*
26Ah
------
------
------
500mA*
* use 2 x 7Ah batteries connected in parallel, UL/ULC installations only
Note:
Battery capacity deteriorates with age and the number of charge/discharge cycles. Replace every 3-5 years.
Refer to See "Regulatory Approvals" on page 208 for detailed Aux. loading and battery charging information.
Connecting AC Power
The alarm controller requires a 16.5V, 40VA transformer. While unplugged, connect the transformer to the AC terminals on
the controller. The alarm controller can be programmed to accept a power line frequency of either 50Hz AC or 60Hz AC. See
programming section [024], option [1].
Note:
For UL/ULC installations use only 60Hz.
Note:
For ULC S559 applications, Standex transformer (Model FTC3716) shall be employed for direct-wiring.
- 28 -