GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
European models only
EUROPEAN MODELS
CAPACITY NOTES
• At sea level, 402 kJ are required to raise the temperature of one kilogram
of water from 4 °C to 100 °C.
• An additional 2257 kJ are required to change the state of one kilogram of
100 °C water to vapor.
• Another factor to consider is condensation steam loss from piping.
LP GAS
All models operate at rated kW input.
OPERATING CHARACTERISTICS
• Unit is capable of operating in ambient conditions of 5 °C to 40 °C.
• Unit is capable of operating in ambient conditions between 30% RH and
95% RH (noncondensing).
• NOx class 5
• Maximum flue temperature under normal operating conditions: 68.3 °C
• Maximum flue temperature safety lockout 82.2°C
GAS SUPPLY PRESSURE
20 or 25 mbar for natural gas (depending on gas group),
and 30, 37 or 50 mbar for propane gas (depending on gas group)
PMS (ALL UNITS)
7.0 bar
ELECTRIC SUPPLY
230V, 667W to 2415W (see data plate)
INLET WATER TEMPERATURE
See Table 34-1.