8
GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Product overview
The GTS humidifier LX series burns either natural or propane gas to heat and
boil fill water into steam for humidification. The unit has either one or two
burners that fire into a heat exchanger submerged in a tank of water. When
there is a call for humidity, the burners fire and generate steam until the call for
humidity ends.
UNIVERSAL WATER
DriSteem's GTS humidifier LX series incorporates universal water control for use
with any water type (well, tap, softened, DI or RO water). There is no need to
change control configurations based on water type when ordering equipment
or retrofitting to fit new water sources in the field. The water level control
algorithm monitors water quality and any changes over time to assure the user
of accurate control no matter the type of water that is used.
Gas connection
Gas valve
Electrical field connection
Primary heat exchanger
Blower
Steam outlet
Control components
Flue gas
vent
Duct dispersion option shown: Ultra-sorb Model LV
OM-7942
Supply water guidelines
Supply water quality is an important component
of humidifier reliability and maintenance.
Examples:
• Corrosive water can decrease the service life
of the humidifier.
• Excessive water hardness can increase the
humidifier maintenance requirements.
To maximize humidifier service life and
minimize humidifier maintenance, DriSteem has
established guidelines for supply water. See
Table 8-1:
DriSteem supply water guidelines
Chlorides*
Tap water
RO/DI water
Softened water
* Damage caused by
chloride corrosion is
not covered by your
DriSteem warranty.
< 50 ppm
< 5 ppm
< 25 ppm
Total hardness
Tap water
< 500 ppm
(29 gpg)
pH
Tap water
RO/DI, softened water
6.5 to 8.5
7.0 to 8.0
Silica
< 15 ppm
Supply water outside of the guidelines
may void your DriSteem warranty.
Please contact your DriSteem
Representative or DriSteem Technical
Support if you need advice.
FIGURE 8-1: GTS HUMIDIFIER LX SERIES
PRODUCT OVERVIEW
Supply water guidelines
Drain
Secondary
heat
exchanger
Combustion air
intake
Air gap
Open drain
Supply
water
connection
Flue gas condensate