37
GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
INSTALLATION
Flue gas condensate
Piping:
FIGURE 37-1: GTS SEALED COMBUSTION CONNECTION - MODELS LX-200 THROUGH LX-600
OM-7995
Notes:
1. Use flexible tubing that is rated for acidic condensate.
2. All tubing must allow flow away for humidifier to condensate
neutralizer (if equipped).
3. Condensate neutralizer should be installed per manufacturer
instructions below the condensate p-trap level.
4. If floor drain is greater than 5' (1.5 m) from humidifier, use a ½"
PVC pipe instead of a hose.
Combustion air intake
Flue gas vent to outside
5/8" (16 mm)
Optional
condensate
neutralizer
5/8" (16 mm) secondary
heat exchanger condensate
Open
drain