GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
FIGURE 53-1: GTS HUMIDIFIER LX SERIES SIDEWALL VENTING
WARNING
Do not exceed the maximum lengths
of the outside vent piping as shown
in Figure 54-1. Excessive length
exposed to the outside could cause
freezing of condensate in the vent
pipe, resulting in potential humidifier
shutdown.
Sidewall venting (continued)
INSTALLATION
OM-7980
Bird screen
Flue gas vent
Bird screen
Bird screen
Combustion air pipe
For Models LX-50 - LX-300 only: Install a drip
tee within the first 3' (1 m) of flue venting for
flue condensate removal. If flue vent is less
than 10' (3 m) long and a sidewall exit, then
no drip tee needed.