65
GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
MAINTENANCE
Inspection and maintenance (continued)
- Water should drain from the skimmer drain pipe after each daily
probe check. This should be verified visually by a weekly inspection.
- Loosen deposits in and around the skimmer/overflow port with a
long tool such as a screwdriver.
- If flow through the water seal/P-trap is diminished due to mineral
accumulation:
- Remove the water seal piping from the humidifier and flush out.
- Replace the water seal with new piping if the minerals have
hardened in the water seal.
• Clean the tank temperature probe — Inspect the probe for mineral
accumulation. The probe is located on the heat exchanger plate just
above the combustion assembly. Use stainless steel wool to clean the
probe.
• Inspect blower motor — A lubrication port is not provided, therefore
lubrication is not required.
• Remove dust — Using a vacuum, remove all dust from areas around the
motor, vent fan(s), and louvers that allow air to the shrouded area.
• When the maintenance requirements are complete:
- Replace cleanout plate and tighten the nuts on the plate. Torque the
nuts to 60 in-lb (6.8 N-m).
Note: Always install a new gasket when the clean out plate is
reassembled.
- Verify that the probe head is secure and that the probe plug and
cable assembly are plugged into the probe rod holder.
- Verify that the drain valve assembly is in the closed position.
• After confirming the plumbing connections are secure, perform a tank
de-scaling procedure using the DriSteem GTS humidifier tank de-scaling
kit.
• When the chemical de-scaling process is complete:
- Replace and secure all covers and doors.
- Turn on the water supply.
- Turn on the electrical power.
- Turn on gas.
- Do not leave humidifier unattended. Allow the humidifier to cycle
through multiple fill cycles and verify that the humidifier cover,
cleanout plate, and probe holder gasket are not leaking.
• Verify proper operation of the humidifier after servicing is complete.
Important:
Minimum supply water pressure is 25 psi
(172 kPa).
WARNING
Prevent wiring errors
When servicing controls, before
disconnecting, label all connections.
Wiring errors can cause explosion or
fire, resulting in severe bodily injury,
death, or significant property damage.