GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
1.
Annually
(also recommended when maintenance is performed)
• Inspect tank, piping, and gaskets for water and gas leaks.
• Inspect condensate lines for blockage and verify condensate neutralizer
is in working condition (pH above 5).
• Inspect venting bird screens for blockage. Clean or replace if damaged.
• All safety devices in the control circuit should be cycled on and off to
verify they are functioning. These include:
- High limit switch
- Airflow proving switch
- Low water level probe. Pull out probe plug; fill valve should energize.
- Flue temperature sensor. Observe the temperature read out on the
Vapor-logic display during normal operation. The temperature will
fluctuate slightly during refill events.
- Tank temperature sensor. Observe the tank temperature read out on
the Vapor-logic home screen during a cold start of the humidifier. The
temperature will gradually increase to boiling temperature.
2.
Seasonally
(or as required, depending on water quality)
• Clean tank
- Drain tank.
- Remove cleanout plate and dispose of any loose scale that has
collected in the tank. Do this before the scale buildup reaches the
bottom of the heat exchanger.
- Inspect the area inside the tank in front of the drain valve fitting and
thoroughly clean all scale and mineral buildup from that area.
- Replace the cleanout plate using new gaskets.
• Dismantle and clean drain valve and associated piping
• Clean the probes
- Access the probe assembly through the round pop cover on the roof
panel.
- Disconnect the probe plug and cable assembly and unscrew the
probe rod assembly from the humidifier probe housing.
- Inspect the probe housing and clean, ensuring that all the housing
passageways are clear.
- The scale should flake off easily from the probe assembly rods.
- The bottom 3/8" (10 mm) of each rod is the sensing portion; clean
these areas with a wire brush, abrasive pad, or steel wool.
- Inspect the composite plastic probe head for any signs of cracking,
roughness, or deterioration. If found, replace entire probe assembly.
- Reassemble the probe assembly.
• Clean the skim/overflow port
WARNING
Follow the shutdown procedure
Follow the shutdown procedure
on Page 60 before performing
service or maintenance procedures
on this humidifier. Failure to follow
the shutdown procedure could cause
electrical shock, fire, or explosion and
severe personal injury or death.
MAINTENANCE
Inspection and maintenance