GTS HUMIDIFIER LX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Location and clearance recommendations
FINDING A LOCATION
• Provide a level, solid foundation for the humidifier.
• The GTS humidifier LX series vent and air piping can be installed through
the roof or through a sidewall. Use only vent/air piping methods described
in this IOM. Locate the humidifier as near as possible to an outside wall
or accessible roof space so that the flue pipe from the humidifier is short,
direct, and limited to wind exposure.
• Locate the unit so it and its electrical components are protected from water
during humidifier operation and service.
• Install the humidifier in a location away (and protected) from drafts. Follow
the instructions concerning combustion and ventilation air.
• Locate the humidifier in an area where leakage from the tank or its
connections will not result in damage to the adjacent structure or to lower
floors of the structure. When such locations cannot be avoided, install
a suitable drain pan (adequately drained) under the humidifier (field
supplied). The pan must not restrict combustion airflow.
• If located in an insulated space, keep the humidifier free and clear of
insulating materials. Insulating material can be combustible. Inspect the
humidifier area when the humidifier is installed or when insulation is
added.
• See the combustion air and flue gas venting section on page 42 for
pipe termination locations and instructions.
INSTALLATION
WARNING
Installation requirements
The humidifier must be installed by
a qualified technician and meet the
requirements of all governing codes.
Failure to follow these instructions could
cause severe bodily injury or death.