4.2- Extinction block connection
4.2.1- Extinction bottle output (BOTTLE)
The extinguishing panel has an output (labeled as BOTTLE) that activates the solenoid
of the extinction equipment. This output allows a total current of 500 mA.
The wiring of this output(1) must begin in the panel socket and end with the end-of-line
module (2) provided with the panel, this module shall be placed as closely as possible
to the solenoid (3) of the extinction bottle.
In case we don’t need to use this output, it is necessary to connect the end-of-line
module in the terminals of the extinction bottle output in order to avoid an output fault
signal from the panel.
Extinction triggering Delay
Just in the lower right part of the panel’s circuit, there is a double strip of pins for
programming the delay of the extinction activation (DELAY EXT). it is possible
to program the the delay from 0 to 60 seconds, placing the jumper in the position
corresponding to the desired time. You can perform and advanced programming
placing the jumper in the PROG position.
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...