4.2.5- Door and bottle surveillance inputs (DOOR, PRESSURE and
FLOW)
The extinguishing panel has two surveillance inputs. One for the surveillance of the
door where it is installed the extinction system, and a second for the surveillance of
the extinction bottle.
The contacts of this outputs must have internally the alarm level resistor (330 Ohm
2W). It is also necessary to place a 4K7 resistor in the end of the line.
In case you don’t want to use all the surveillance inputs, you have to place the end-
of-line resistor in the not used input terminals in order to avoid an input fault from the
system.
4.2.6- Connexion of the open collector outputs
Open collector output to indicate:
Pin
Iddle
Activated
Only Manual Mode
2
0
1
Disconnected
3
0
1
Abort MCP
4
0
1
Hold MCP
5
0
1
Start MCP
6
0
1
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...