34
GB
This central has a user friendly design.
Through some programmable options, the performance of the central can be modified
to suit different countries demands and performing methods of the fire extinguishing
systems.
Some of this programmable options doesn’t comply the EN54
For entering the programming mode, the jumper PROG must be switched ON.. In this
state the central will conmute the display and the numeral parameter to be configured.
From the P01 parameter until the P99, and the according value to the selected
parameter.
The following keys are used to navigate through the centrals’ option settings
:
•
Pushing the Key “Test” we’ll increase the programmable parameter.
•
Pushing the Key “activate Sirens” we’ll decrease the programmable parameter.
•
Pushing the key “ Silence Sirens” we’ll increase the value of the parameter.
•
Pushing the key “ Silence Buzzer” we’ll decrease the value of the parameter.
•
Pushing the key “Reset” we’ll save and validate the parameter.
8.1- Extinction Delay configuration (F01)
The existing delay between the “activated” state and the “triggered” state is configurable
by means of the “DELAY EXT” jumper. This jumper allows to select a predefined time
from 0 to 60 seconds in steps of 5 seconds. It If the last position (PROG) is selected,
the delay value will be the stored in the P01 parameter position of the configuration
system. This is a programmable value, the range for this value goes from 0 to 999
seconds. The default value is 60 seconds.
8.2.- Flooding time configuration (F02)
The elapsed time between the “triggered” state and the “end of triggering” state is
stored in the P02 parameter. This value is programmable. The range for this value
goes from 2 to 300 seconds, the default value is 60 seconds.
8 - Setting options
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...