Same as the case stated before but without starting the extinction. This state must be
indicated in less than 2 seconds after its selection.
In this mode ,the extinction just starts in Manual Mode, according to the different
functions of each push button.
Access to Canceled Mode:
•
Selectable with the 3 positions switch.
•
Stated with its corresponding led.
•
Activates the digital output “Only Manual Mode”.
6.6- States of the extinction process
The extinction block can be in four different states:
Sleep, Pre-activated, Activated, Triggered, Triggering Ended.
6.6.1- Extinction Sleep State
The central hasn’t started any extinction process (manual or automatic). In this state
there must be only two leds active: the corresponding to the operating mode selected
and the green service led.
In case of fault of any of the supervised inputs or outputs, it will be displayed through
the activation of the main fault relay.
6.6.2- Pre-Activated Extinction state (First State)
Este estado indica que hay una alarma en la Zona 1 o la Zona 2 En este estado la
central realiza las siguientes acciones:
•
Pre-activeted state indicator (first state).
•
Siren On indicator State 1.
•
Sirens’ output activation State 1:
0.5 Hz frequency.
•
Acoustic indicator:
continuously.
•
Display activation:
Shows the programmed time until the triggering of the extinction.
Once the Preactivated state is reached, following actions may be carried out:
•
Pushing the central Silence Key:
Silences the buzzer and activates the indicator
of Silenced buzzer.
•
Pushing the reset key:
the system wil go back to sleep mode. It is not recommended
to reset the system until the alarm cause is found.
•
Activation of the Manual external push buttons
.
6.6.3- Activated Extinction Mode.
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...