3.3.6.2- Battery connection
The extinguishing panel requires two 12V batteries. The housing takes 12V 2.3A/h and
12V 7A/h batteries for the central units. The batteries must be connected in series for
the proper functioning of the panel.
The cable supplied with the unit must be connected so that the positive terminal of one
battery is connected with the negative terminal of the other. The batteries are placed
in the bottom of the box, in the space reserved for this purpose. Place the 12V 2.3A/h
batteries horizontally or the 12V 7A/h batteries vertically.
Connect the wires from the circuit (red and black) to the unused positive and negative
terminals of the two batteries. Remember to connect the batteries together first, using
the battery bridge cable.
Summary of Contents for CCD-103
Page 1: ...GB ES ES GUIDE MANUAL FR 3 Zones Conventional fire extinguishant control panel IT ...
Page 2: ......
Page 3: ...ES ES Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL DEL USUARIO ...
Page 4: ......
Page 6: ......
Page 14: ...12 ES 4 Guía de conexionado de la PCB ...
Page 44: ......
Page 45: ...GB GUIDE MANUAL 3 Zones Conventional fire extinguishant control panel ...
Page 46: ......
Page 48: ......
Page 56: ...12 GB 4 PCB connection guide ...
Page 86: ......
Page 87: ...FR FR Centrale conventionnelle à 3 zones de détection et 1 zone d extinction MODE D EMPLOI ...
Page 88: ......
Page 90: ......
Page 98: ...FR 12 4 Guide de branchement de la PCB carte de circuit imprimé ...
Page 128: ......
Page 129: ...IT Central Convencional de 3 Zonas de detección y 1 Extinción MANUAL UTENTE ...
Page 130: ......
Page 132: ......
Page 140: ...12 IT 4 Guía de conexionado de la PCB ...
Page 170: ...55310300 2014 10 14 ...